A study of building structural features associated with high indoor air concentrations of organochlorine termiticides

Aust J Public Health. 1993 Sep;17(3):237-40. doi: 10.1111/j.1753-6405.1993.tb00142.x.

Abstract

As part of a two-year study of post-treatment residential exposure to the termiticide, aldrin, the building structural features of ten houses with crawl-space-type floors were assessed by an independent inspector. Building attributes recorded on a checklist included the age of the dwelling, room characteristics, floor details and the nature of subfloor ventilation. At the end of each inspection, the inspector, who was blinded to data on airborne aldrin concentrations, provided a rating of expected indoor air contamination. Several of the building attributes, including the age of the house, the area of exterior subfloor vents, as well as the inspector's rating, were significantly correlated with airborne aldrin values. No single building variable, however, was highly correlated with every measure of aldrin concentration over a 12-month period. The observed data are consistent with poor subfloor ventilation and a 'leaky' floor being important contributors to indoor air pollution. It is recommended that pest control companies advise householders about any obvious floor and ventilation deficiencies before soil treatment work is undertaken. Pesticide exposure (by analogy with geological radon exposure) may be reduced by sealing gaps in floors and/or by improving subfloor ventilation.

Publication types

  • Research Support, Non-U.S. Gov't

MeSH terms

  • Air Pollution, Indoor / analysis*
  • Aldrin / analysis*
  • Facility Design and Construction*
  • Housing

Substances

  • Aldrin