Low-cost interventions to improve ventilation in long-term care facilities

J Occup Environ Hyg. 2024 Apr 23:1-10. doi: 10.1080/15459624.2024.2328295. Online ahead of print.

Abstract

Residents of long-term care facilities are particularly vulnerable to communicable diseases. Low-cost interventions to increase air exchange rates (AERs) may be useful in reducing the transmission of airborne communicable diseases between long-term care residents and staff. In this study, carbon dioxide gas was used as a tracer to evaluate the AER associated with the implementation of low-cost ventilation interventions. Under baseline conditions with the room's door closed, the mean AER was 0.67 ACH; while baseline conditions with the door open had a significantly higher mean AER of 3.87 ACH (p < 0.001). Subsequently opening a window with the door open increased mean AER by 1.49 ACH (p = 0.012) and adding a fan in the window further increased mean AER by 1.87 ACH (p < 0.001). Regression analyses indicated that the flow rate of air entering through the window, both passively and through the use of a fan, was significantly associated with an increase in AER (p < 0.001). These results indicate that low-cost interventions that pull outside air into resident rooms were effective in improving the air exchange rates in these facilities. While implementation of these interventions is dependent on facility rules and isolation requirements of residents with airborne communicable diseases, these interventions remain viable options for long-term care facilities to improve resident room ventilation without requiring costly ventilation system upgrades.

Keywords: Air exchange rate; airborne communicable diseases; indoor air quality; occupational hygiene.