A Comparative Study of Abnormal Heating Composite Insulators

Polymers (Basel). 2023 Jun 21;15(13):2772. doi: 10.3390/polym15132772.

Abstract

The abnormal heating of composite insulators on transmission lines frequently occurs, seriously threatening the power grid's safe and stable operation. For different types of abnormal heating composite insulators, undifferentiated replacement wastes a lot of labor and material resources. This study explores the abnormal heating composite insulators under different environmental humidity and wind speed conditions. The heating and discharge of composite insulators are observed, and the heating range, heating shape, and temperature rise (ΔT) are analyzed. The abnormal heating of the sheath-aging composite insulator is related to the aging of the silicone rubber and the environmental humidity. The partial discharge caused by the core rod's defect is the primary source of the temperature rise in the decay-like insulator. The heating range of the contaminated insulator is connected to the environmental humidity, and the ΔT increases with the salt density. The ΔT and heating range of the three types of abnormal heating increase with the ambient humidity. The heating phenomenon under low humidity is an important characteristic that distinguishes decay-like and contaminated insulators from sheath-aging insulators. Therefore, the on-site infrared inspection should be carried out in sunny and windless weather to prevent the impact of high humidity and wind speed on infrared temperature measurement.

Keywords: abnormal heating; composite insulator; infrared thermal image; temperature characteristic.