Degradation and Lifetime Prediction of Epoxy Composite Insulation Materials under High Relative Humidity

Polymers (Basel). 2023 Jun 13;15(12):2666. doi: 10.3390/polym15122666.

Abstract

Insulation failure of composite epoxy insulation materials in distribution switchgear under the stress of heat and humidity is one of the leading causes of damage to switchgear components. This work prepared composite epoxy insulation materials by casting and curing a diglycidyl ether of bisphenol A (DGEBA)/anhydride/wollastonite composite system, and performed material accelerated aging experiments under three conditions: 75 °C and 95% relative humidity (RH), 85 °C and 95% RH, and 95 °C and 95% RH. Material, mechanical, thermal, chemical, and microstructural properties were investigated. Based on the IEC 60216-2 standard and our data, tensile strength and ester carbonyl bond (C=O) absorption in infrared spectra were chosen as failure criteria. At the failure points, the ester C=O absorption decreased to ~28% and the tensile strength decreased to 50%. Accordingly, a lifetime prediction model was established to estimate material lifetime at 25 °C and 95% RH to be 33.16 years. The material degradation mechanism was attributed to the hydrolysis of epoxy resin ester bonds into organic acids and alcohols under heat and humidity stresses. Organic acids reacted with calcium ions (Ca2+) of fillers to form carboxylate, which destroyed the resin-filler interface, resulting in a hydrophilic surface and a decrease in mechanical strength.

Keywords: degradation mechanism; epoxy composite; lifetime prediction model; material properties.