Evaluating Manual Sampling Locations for Regulatory and Emergency Response

J Water Resour Plan Manag. 2021 Sep 24;147(12):1-11. doi: 10.1061/(asce)wr.1943-5452.0001473.

Abstract

Drinking water systems commonly use manual or grab sampling to monitor water quality, identify or confirm issues, and verify that corrective or emergency response actions have been effective. In this paper, the effectiveness of regulatory sampling locations for emergency response is explored. An optimization formulation based on the literature was used to identify manual sampling locations to maximize overall nodal coverage of the system. Results showed that sampling locations could be effective in confirming incidents for which they were not designed. When evaluating sampling locations optimized for emergency response against regulatory scenarios, the average performance was reduced by 3%-4%, while using optimized regulatory sampling locations for emergency response reduced performance by 7%-10%. Secondary constraints were also included in the formulation to ensure geographical and water age diversity with minimal impact on the performance. This work highlighted that regulatory sampling locations provide value in responding to an emergency for these networks.

Keywords: Drinking water distribution system modeling; Grab sampling; Optimization; Sample site selection; WNTR.