Ventilation improvement and evaluation of its effectiveness in a Japanese manufacturing factory

Sci Rep. 2022 Oct 21;12(1):17642. doi: 10.1038/s41598-022-22764-2.

Abstract

A coronavirus disease 2019 (COVID-19) cluster emerged in a manufacturing factory in early August 2021. In November 2021, we conducted a ventilation survey using the tracer gas method. Firstly, we reproduce the situation at the time of cluster emergence and examined whether the ventilation in the office was in a condition that increased the risk of aerosol transmission. Secondly, we verified the effectiveness of the factory's own countermeasure implemented immediately after the August cluster outbreak. Furthermore, we verified the effectiveness of several additional improvement measures on the factory's own countermeasures already installed in August. Under the conditions of the cluster emergence, the air changes per hour (ACH) value was 0.73 ACH on average. The ACH value was less than 2 ACH recommended by the Ministry of Health, Labour, and Welfare, suggesting an increased risk of aerosol transmission. The factory's own countermeasures taken immediately in August were found to be effective, as the ACH value increased to 3.41 ACH on average. Moreover, it was confirmed that additional improvement measures on the factory's own countermeasures increased the ACH value to 8.33 ACH on average. In order to prevent the re-emergence of COVID-19 clusters due to aerosol infection in the office, it was found that while continuing the factory's own countermeasure, additional improvement measures should also be added depending on the number of workers in the room. In a company, it is important that workers themselves continue to take infection control measures autonomously, and confirming the effectiveness of the measures will help maintain workers' motivation. We believe it is helpful that external researchers in multiple fields and internal personnel in charge of the health and safety department and occupational health work together to confirm the effectiveness of conducted measures, such as in this case.

Publication types

  • Research Support, Non-U.S. Gov't

MeSH terms

  • COVID-19* / epidemiology
  • COVID-19* / prevention & control
  • Humans
  • Japan / epidemiology
  • Manufacturing and Industrial Facilities
  • Respiratory Aerosols and Droplets
  • Ventilation