Investigation of the Optimal Operating Position of an Air Cleaner in Terms of Indoor Air Quality in a Four-Bed Hospital Ward

Toxics. 2022 Jun 30;10(7):360. doi: 10.3390/toxics10070360.

Abstract

The use of air cleaners indoors has increased with the increase in indoor activities driven by the COVID-19 outbreak. In this study, the indoor air quality was determined at the location of each patient's respirator in a four-bed hospital ward equipped with a ventilation system and curtains, by varying the position of one air cleaner. By operating the air cleaner alone without the ventilation system, it was confirmed that it is better to place the air cleaner close to the center of the ward, regardless of whether curtains are used. It was further identified that the farther away the air cleaner is from the center, the worse the age of air could be, compared to the case of operating it in the center. Moreover, the situation where the ventilation system and air cleaner were operated simultaneously in the hospital ward was considered. It was discovered that operating the air cleaner close to the ventilation inlets in the absence of curtains helps to improve the indoor air quality. Furthermore, it was found that the age of the air is generally low near the location where the air cleaner is operated in the presence of curtains. Selecting an optimal position for the air cleaner can improve the air quality at the location of each bed in a four-bed hospital ward.

Keywords: age of air; air cleaner; hospital ward; indoor air quality; ventilation system.