PD Flexible Built-In High-Sensitivity Elliptical Monopole Antenna Sensor

Sensors (Basel). 2022 Jul 1;22(13):4982. doi: 10.3390/s22134982.

Abstract

In view of the insufficient signal detection sensitivity of Gas Insulated Switchgear (GIS), partial discharge (PD), ultra-high frequency (UHF), and failure to conform with GIS surface structure when the existing rigid stereo structure UHF sensor is built in, this paper, using rectangular patch antenna equivalent technique, trapezoidal ground plane technique, and coplanar waveguide (CPW) feed line index asymptotic linearization technique, conducts research on a flexible built-in high-sensitivity elliptic monopole antenna. The flexible antenna, with a thickness of only 0.28 mm, can be kept at a voltage standing wave ratio (VSWR) of less than three in the 300 MHz to 3 GHz band under the curvature radius of 0, 100, 300, and 500 mm, and at less than two in the 650 MHz to 3 GHz band. Through the true 220 kV-GIS partial discharge experimental platform built to analyze the high frequency electromagnetic wave detection performance of the built-in flexible antenna, it is shown that the flexible built-in high-sensitivity elliptical monopole antenna designed in this paper can effectively detect the characteristic signals of high-frequency electromagnetic waves emitted by partial discharges with an average discharge amount below 10 pC.

Keywords: Gas Insulated Switchgear; flexible antenna; monopole antenna; partial discharge; ultra-high frequency.