Heating performance of a laboratory pilot-plant combining heat exchanger and air scrubber for animal houses

Sci Rep. 2021 Mar 25;11(1):6872. doi: 10.1038/s41598-021-86159-5.

Abstract

Exhaust air treatment systems (EATS) are used in animal husbandry to reduce emissions. However, EATS are associated with high acquisition and operating costs. Therefore, a plant technology is being developed that integrates a recuperative heat exchanger into a biological air scrubber. The overall aim is to reduce total costs of livestock buildings with EATS by saving heating costs and to improve animal environment. In this study, a special pilot-plant on a small-scale, using clean exhaust air, was constructed to evaluate the heating performance on laboratory scale. Three assembly situations of the heat exchanger into trickle-bed reactor were part of a trial with two different defined air flow rates. In all three assembly situations, preheating of cold outside air was observed. The heating performance of the assembly situation with the sprayed heat exchanger arranged below showed an average of 4.4 kW at 1800 m3 h-1 (outside air temperature range 0.0-7.9 °C). This is up to 18% higher than the other two experimental setups. The heating performance of the pilot-plant is particularly influenced by the outside air temperature. Further research on the pilot-plant is required to test the system under field conditions.

Publication types

  • Research Support, Non-U.S. Gov't