Implementing a negative pressure isolation space within a skilled nursing facility to control SARS-CoV-2 transmission

Am J Infect Control. 2021 Apr;49(4):438-446. doi: 10.1016/j.ajic.2020.09.014. Epub 2020 Oct 3.

Abstract

Background: Isolation space must be expanded during pandemics involving airborne transmission. Little to no work has been done to establish optimal design strategies and implementation plans to ease surge capacity and expand isolation capacity over long periods in congregate living facilities. The COVID-19 pandemic has an airborne transmission component and requires isolation, which is difficult to accomplish in skilled nursing facilities.

Methods: In this study we designed, implemented, and validated an isolation space at a skilled nursing facility in Lancaster, PA. The overall goal was to minimize disease transmission between residents and staff within the facility. We created an isolation space by modifying an existing HVAC system of the SNF. We measured pressure on-site and performed computational fluid dynamics and Lagrangian particle-based modeling to test containment and possible transmission extent given the isolation space is considered negative rather than individual rooms.

Results: Pressure data shows the isolation space maintained an average (standard deviation) hourly value of -2.3 Pa (0.12 Pa) pressure differential between it and the external hallway connected to the rest of the facility. No transmission of SARS-CoV-2 between residents isolated to the space occurred, nor did any transmission to the staff or other residents occur. The isolation space was successfully implemented and, as of writing, continues to be operational through the pandemic.

Conclusion: Skilled nursing facilities can be retrofitted to provide negative pressure isolation space in a reasonable time frame and a cost effective manner to minimize airborne disease transmission within that space.

Keywords: Aerosol transmission; Airborne transmission; Congregate living facilities; Engineering controls; Surge capacity.

MeSH terms

  • COVID-19 / prevention & control*
  • Humans
  • Patient Isolation*
  • SARS-CoV-2*
  • Skilled Nursing Facilities*