Hexavalent Chromium Release in Drinking Water Distribution Systems: New Insights into Zerovalent Chromium in Iron Corrosion Scales

Environ Sci Technol. 2020 Oct 20;54(20):13036-13045. doi: 10.1021/acs.est.0c03922. Epub 2020 Sep 30.

Abstract

Upon cast iron corrosion in contact with residual disinfectants, drinking water distribution systems have become potential geogenic sources for hexavalent chromium Cr(VI) release. This study investigated mechanisms of Cr(VI) release from cast iron corrosion scales. The oxidation of the corrosion scales by residual disinfectant chlorine released Cr(VI) and exhibited a three-phase kinetics behavior: an initial 2 h fast reaction phase, a subsequent 2-to-12 h transitional phase, and a final 7-day slow reaction phase approximately 2 orders of magnitude slower than the initial phase. X-ray absorption spectroscopy analysis discovered that zerovalent Cr(0) coexisted with trivalent Cr(III) solids in the corrosion scales. Electrochemical corrosion analyses strongly suggested that Cr(0) in the corrosion scales originated from Cr(0) in the cast iron alloy. Cr(0) exhibited a much higher reactivity than Cr(III) in the formation of Cr(VI) by chlorine. The presence of bromide in drinking water significantly accelerated Cr(VI) release because of its catalytic effect. Meanwhile, chlorine consumption was mainly attributed to the oxidation of organic matter and ferrous iron. Findings from this study point to a previously unknown but important pathway of Cr(VI) formation in drinking water, that is, direct oxidation of Cr(0) by chlorine, and suggest new strategies to control Cr(VI) in drinking water by inhibiting Cr(0) reactivity.

Publication types

  • Research Support, U.S. Gov't, Non-P.H.S.

MeSH terms

  • Chromium / analysis
  • Corrosion
  • Drinking Water*
  • Iron
  • Oxidation-Reduction
  • Water Pollutants, Chemical* / analysis

Substances

  • Drinking Water
  • Water Pollutants, Chemical
  • Chromium
  • chromium hexavalent ion
  • Iron