Microbiological examination of water and aerosols from four industrial evaporative cooling systems in regard to risk of Legionella emissions and methodological suggestions for surveillance

Int J Hyg Environ Health. 2020 Aug:229:113591. doi: 10.1016/j.ijheh.2020.113591. Epub 2020 Aug 19.

Abstract

The hygienic risk associated with evaporative cooling systems in Germany is currently only assessed by determining concentrations of Legionella spp. in the corresponding cooling waters. Relevant for the health risk is however the load of Legionella in emitted aerosols. In this work aerosol emissions from four industrial cooling systems (A - D) were analyzed. A microbiological air bioburden factor (MABF) is suggested to be useful to assess the overall microbiological load of emitted air and to judge the efficiency of droplet separation and overall microbiological retention. Whereas the MABF by itself only serves as a technical quality assurance (QA) parameter, the hygienic relevance has to be seen in combination with the assessment of Legionella either contained in the aerosol or in the cooling water. Plate counting of colonies was an appropriate method to quantify Legionella spp. in aerosols given the short time of flight at the chosen sampling locations and resulting low risk of desiccation. qPCR data on the other hand proved more reproducible than the culture approach to quantify Legionella spp. concentrations in cooling water-. The application of qPCR also allowed to assess the relative proportion of Legionella pneumophila within the total pool of Legionella which adds epidemiological relevance to risk assessment. A traffic light system was proposed to guide interpretation of qPCR data. The four industrial systems greatly differed in all measured parameters leading to different associated risks.

Keywords: Aerosols; Air bioburden; Evaporative cooling systems; Legionella; Legionella risk assessment.

Publication types

  • Research Support, Non-U.S. Gov't

MeSH terms

  • Aerosols
  • Air Conditioning*
  • Air Pollutants / isolation & purification*
  • Environmental Monitoring
  • Industry
  • Legionella / genetics
  • Legionella / isolation & purification*
  • Risk Assessment
  • Water Microbiology*

Substances

  • Aerosols
  • Air Pollutants