Effect of ventilation rate on air cleanliness and energy consumption in operation rooms at rest

Environ Monit Assess. 2018 Feb 27;190(3):178. doi: 10.1007/s10661-018-6556-z.

Abstract

The interrelationships between ventilation rate, indoor air quality, and energy consumption in operation rooms at rest are yet to be understood. We investigate the effect of ventilation rate on indoor air quality indices and energy consumption in ORs at rest. The study investigates the air temperature, relative humidity, concentrations of carbon dioxide, particulate matter (PM), and airborne bacteria at different ventilation rates in operation rooms at rest of a medical center. The energy consumption and cost analysis of the heating, ventilating, and air conditioning (HVAC) system in the operation rooms at rest were also evaluated for all ventilation rates. No air-conditioned operation rooms had very highest PM and airborne bacterial concentrations in the operation areas. The bacterial concentration in the operation areas with 6-30 air changes per hour (ACH) was below the suggested level set by the United Kingdom (UK) for an empty operation room. A 70% of reduction in annual energy cost by reducing the ventilation rate from 30 to 6 ACH was found in the operation rooms at rest. Maintenance of operation rooms at ventilation rate of 6 ACH could save considerable amounts of energy and achieve the goal of air cleanliness.

Keywords: Air cleanliness; Energy consumption; Indoor air quality; Operation room; Particulate matter; Ventilation rate.

MeSH terms

  • Air Conditioning
  • Air Pollution, Indoor / analysis*
  • Bacteria / isolation & purification*
  • Carbon Dioxide / analysis
  • Environmental Monitoring*
  • Humans
  • Operating Rooms*
  • Particulate Matter / analysis*
  • Temperature
  • United Kingdom
  • Ventilation / methods*

Substances

  • Particulate Matter
  • Carbon Dioxide