Impact assessment of odours emitted by a wastewater treatment plant

Water Sci Technol. 2012;66(10):2223-8. doi: 10.2166/wst.2012.409.

Abstract

Complaints from the Domingos Martins population about sewage odours in the city made the district attorney order an impact assessment of the odours emitted by the city wastewater treatment plant (WWTP). This study comprised various techniques, models and population surveys. In 2007, an odour emission model proved that the main hydrogen sulphide emitter was the aeration tank of the WWTP (13.5 g h(-1)) and such emissions, according to CALPUFF model, should be perceived in the whole Domingos Martins city centre area. In this area, 58% of those interviewed were annoyed by the WWTP odours. However, in 2009, the odour monitoring panel recorded few odour occurrences. A second population survey showed that hereafter only 20% of those interviewed were annoyed by the WWTP emissions. Odour emission and dispersion models run with 2010 data proved a drastic reduction of the WWTP aeration tank emissions and consequently the city centre was not bothered by WWTP emissions anymore. The odour emission reduction was due to the modification of the WWTP aeration tank system. Despite the odour emission reduction, houses located southeast of the WWTP were still annoyed by sewage odours. However, in this part of the town, other sources of sewage odours have been found.

MeSH terms

  • Brazil
  • Cities
  • Environment*
  • Environmental Monitoring*
  • Humans
  • Hydrogen Sulfide
  • Odorants*
  • Time Factors
  • Waste Disposal, Fluid*
  • Wind

Substances

  • Hydrogen Sulfide