Optimal sensor location design for reliable fault detection in presence of false alarms

Sensors (Basel). 2009;9(11):8579-92. doi: 10.3390/s91108579. Epub 2009 Oct 27.

Abstract

To improve fault detection reliability, sensor location should be designed according to an optimization criterion with constraints imposed by issues of detectability and identifiability. Reliability requires the minimization of undetectability and false alarm probability due to random factors on sensor readings, which is not only related with sensor readings but also affected by fault propagation. This paper introduces the reliability criteria expression based on the missed/false alarm probability of each sensor and system topology or connectivity derived from the directed graph. The algorithm for the optimization problem is presented as a heuristic procedure. Finally, a boiler system is illustrated using the proposed method.

Keywords: directed graph; false alarm; fault detection; missed alarm; reliability.