Identifying the performance and losses of a scroll compressor with vapour injection and R1234ze(E)

Open Res Eur. 2022 Nov 28:2:49. doi: 10.12688/openreseurope.14658.2. eCollection 2022.

Abstract

This work investigates a vapour injection scroll compressor integrated in a heat pump using the refrigerant R1234ze(E). The water-to-water heat pump was tested under a wide temperature range at the evaporator and condenser sides. The test results revealed that the performance is significantly reduced for lifts of over 30 K with the coefficient of performance being even below 2 and the maximum 2 nd law efficiency was just 28%. In order to enlighten the reasons behind such significant compressor underperformance, a semi-empirical model has been extended to include vapour injection, and a new improved modelling approach for the suction pressure drop was developed and implemented considering both the turbulent and laminar inlet flow regimes. Once the accuracy of the developed semi-empirical model was verified, the model was then adjusted to account for the R1234ze(E) operation, by fine-tuning its parameters based on the test data. The main loss mechanism identified is the high suction pressure drop, due to the high friction factor, with the inlet refrigerant flow possibly being laminar instead of turbulent. This resulted in a significant reduction of the mass flow rate and volumetric efficiency, while the standard model for suction pressure drop was not able to capture this effect.

Keywords: HFO refrigerant; R1234ze(E); heat pump; scroll compressor; semi-empirical model; suction pressure drop; vapour injection.

Grants and funding

This work has been implemented within the Renewables for clean energy buildings in a future power system (RES4BUILD) project that has received funding from the European Climate, Infrastructure and Environment Executive Agency (CINEA) under the European Union’s Horizon 2020 research and innovation programme (grant agreement No 814865).