Derivation of Corrosion Depth Formula According to Corrosion Factors in District Heating Water through Regression Analysis

Materials (Basel). 2023 Apr 20;16(8):3254. doi: 10.3390/ma16083254.

Abstract

In order to predict the corrosion depth of a district heating pipeline, it is necessary to analyze various corrosion factors. In this study, the relationship between corrosion factors such as pH, dissolved oxygen, and operating time and corrosion depth was investigated using the Box-Behnken method within the response surface methodology. To accelerate the corrosion process, galvanostatic tests were conducted in synthetic district heating water. Subsequently, a multiple regression analysis was performed using the measured corrosion depth to derive a formula for predicting the corrosion depth as a function of the corrosion factors. As a result, the following regression formula was derived for predicting the corrosion depth: "corrosion depth (μm) = -133 + 17.1 pH + 0.00072 DO + 125.2 Time - 7.95 pH × Time + 0.002921 DO × Time".

Keywords: carbon steel; galvanostatic test method; long-term corrosion; underground infrastructure; weldment.