Abstract

An optical DC current transformer anomaly handling mechanism is proposed to address the problem that the conventional DC current transformer anomaly handling mechanism cannot compensate for the defect of capacitor anomaly blocking. First, the implementation principle, modulation loop, demodulation method and its anomaly warning mechanism of the sine-wave modulated all-fibre-optic current transformer (FOCT) are investigated, and the effects of light source intensity and modulation voltage on current decoding are explained. The modulation loop is then simulated and modelled and a FOCT anomaly handling mechanism is proposed based on the Bessel function with real-time dynamic current compensation for small changes in modulation depth. Finally, an integrated dynamic test system for DC current transformers and DC protection is designed, and the actual system operation and fault model is established using the RTDS simulation system. The experiments demonstrate that the proposed FOCT anomaly handling and improvement measures can effectively improve the transient performance of FOCT, and at the same time provide a complete set of testing means for the engineering application and later upgrade and replacement of FOCT.

Keywords: Abnormal handling mechanism; Bessel function; Compensation circuit; FOCT; Modulation circuit; Transient test system.

Grants and funding

This work was supported by the Science and Technology Project of State Grid Jiangxi Electric Power Co., Ltd (52182020008J). The funders had no role in study design, data collection and analysis, decision to publish, or preparation of the manuscript.