Evaluation of Various Ejector Profiles on CO2 Transcritical Refrigeration System Performance

Entropy (Basel). 2022 Aug 23;24(9):1173. doi: 10.3390/e24091173.

Abstract

This study examines the potential impact of the different ejector profiles on the CO2 transcritical cooling system to highlight the contribution of the multi-ejector in the system performance improvement. The research compares the implementation of an ejector-boosted CO2 refrigeration system over the second-generation layout at a motive flow temperature of 35 °C and discharge pressure of 90 bar to account for the transcritical operation mode. The result revealed a significant energy saving by reducing the input power to the maximum of 8.77% when the ejector was activated. Furthermore, the multi-ejector block could recover up to 25.4% of the expansion work losses acquired by both ejector combinations VEJ1 + 2. In addition, the behavior of the multi-ejector geometries and operation conditions greatly influence the system exergy destruction. The analysis shows a remarkable lack of exergy destruction during the expansion process by deploying the ejector in parallel with the HPV.

Keywords: COP; R744; ejector; exergy destruction; power consumption.