Effect of the B:Zn:H2O Molar Ratio on the Properties of Poly(Vinyl Acetate) and Zinc Borate-Based Intumescent Coating Materials Exposed to a Quasi-Real Cellulosic Fire

Polymers (Basel). 2020 Oct 30;12(11):2542. doi: 10.3390/polym12112542.

Abstract

In order to investigate an influence of the B:Zn:H2O molar ratio on the fire protection efficiency of poly(vinyl acetate)-based thermoplastic intumescent coating materials (ICs), systems containing ammonium polyphosphate, melamine, pentaerythritol and different types of zinc borates (ZBs) were tested in a vertical position in quasi-real fire conditions. 3ZnO·2B2O3·6H2O (ZB6), 2ZnO·3B2O3·3.5H2O (ZB3.5) or 3ZnO·2B2O3 (ZB0) were added in amounts of 1-10 wt. parts/100 wt. parts of the other coating components mixture. Char formation processes and thermal insulation features were investigated using an open-flame furnace heated according to the cellulosic fire curve. Thermogravimetric features (DTG), chemical structures (FTIR) and mechanical strength of the ICs and the chars were analyzed as well. It was revealed that the type and dose of the ZBs significantly affect thermal insulation time (TIT) (up to 450 °C of a steel substrate) and sagging (SI) of the fire-heated coatings as well as the compressive strength of the created chars. The highest TIT value (+89%) was noted for the sample with 2.5 wt. parts of ZB3.5 while the lowest SI (-65%) was observed for the coatings containing 10 wt. parts of the hydrated borates (i.e., ZB3.5 or ZB6). The best mechanical strength was registered for the sample filled with the anhydrous modifier (3 wt. parts of ZB0). The presented results show that the ICs with the proper ZBs can be used for effective fire protection of vertically positioned steel elements.

Keywords: cellulosic fire; flame retardancy; intumescent coating; poly(vinyl acetate); zinc borate.