Operational experience with a full-scale anaerobic baffled reactor treating municipal wastewater

Water Environ Res. 2019 Jan;91(1):54-68. doi: 10.2175/106143017X15131012188295.

Abstract

The aim of the study was to investigate the influence of moderate temperatures on the efficiency of a full-scale anaerobic treatment system consisting of a primary sedimentation unit (PST) and an anaerobic baffled reactor (ABR, approx. 10 m3 ). Therefore, two trials with different test setups in series were carried out (1st trial: continuous load; 2nd trial: diurnal variation load). The plant was fed with municipal wastewater and operated at temperatures between 8 and 24°C. The mean efficiency of the ABR was low, compared to the one of the PST. At 10°C, only 10% of the COD was removed. The COD (chemical oxygen demand) removal efficiency of the plant (PST + ABR) averaged 50%. At low temperatures, volatile fatty acids began to accumulate. In both trials, the contents of total suspended solids in the sludge bed differed distinctly and influenced the effort for desludging. PRACTITIONER POINTS: The operation of ABR in combined collection systems depends on the efficiency of the pretreatment unit. At cold temperatures, an ABR has no advantages compared to conventional pretreatment processes. For use under moderate conditions, the design must be adjusted.

Keywords: anaerobic baffled reactor; anaerobic process; efficiency; moderate temperatures; sludge digestion; temperature impact; volatile fatty acids.